Exterior Doors: LCN 4041 Series (No Substitutions Allowed)
Interior Doors: LCN 1461 Series (No Substitutions Allowed)
All door closers shall be mounted on the interior side of the room.
All door closers shall be equipped with “Delayed Action” feature.
8) All lock hardware must accept BEST 7 pin, interchangeable cores.
9) All interior door hardware shall be BEST 45H mortise or 9K cylindrical locks.
10) All access control system control panels shall be mounted within a telecom closet. All
cabling shall be installed as to “Home Run” back to this area. Proper room shall be
allocated for necessary equipment. Circuits supplying AC voltage to the access control
system shall NOT provide power to any other system or devices.
11) Any door that is monitored by access control system, but does not have a card reader shall
have a PIR (Motion Detector) or RQE (request to exit) device to mask exiting traffic.
12) All power supplies and access control support systems shall be installed and connected to
the buildings Emergency Back-up Generator in addition to Battery Back-up.
13) Magnetic locks (mag locks) and/or Electric strikes shall NOT be used.
14) All Access Control power supplies shall be clearly labeled as to the door designation,
electrical panel, and circuit number from which it is supplied.
15) Doors and frames shall accept an EPT (Electrified Power Transfer). Electrified hinges
should not be used.
END OF DOCUMENT