Installation Instructions for 34HW–35HW IDH Max Mortise Locks
BEST ACCESS SYSTEMS
Indianapolis, Indiana
Installing the panel interface module
22
Sounder input configuration
Provides the ability to invert the interpretation of the sounder input signal.
The normal input configuration interprets a closed contact as sounder ON.
Normal input Switch 7–ON
Inverted input Switch 7–OFF
Function of TPR terminals and DLS terminals
Provides the ability to determine the function of the TPR terminals and
DLS terminals, as shown below.
Option 1 Switch 8–ON
Option 2 Switch 8–OFF
Feature Option DIP Switch Setting
Configuration
option
Function of
TPR terminals
Function of
DLS terminals
Option 1
(Switch 8–ON)
Communications
tamper
Door status &
latch status
Option 2
(Switch 8–OFF
Latch status Door status